Three-Phase Power Calculator – P = √3 × Line Voltage × Line Current × pf
Use this free Three-Phase Power Calculator to find the total real power in a balanced three-phase system from the line voltage, line current and power factor. The calculator also shows the power handled by each individual phase.
Formula
Total power: P = √3 × VL × IL × cos φ • power per phase: Pphase = P / 3 • for a star (Y) load, Vphase = VL/√3 and Iphase = IL.
How to use
- Enter the line-to-line voltage (400 V in most industrial systems, 208 V or 480 V in North America).
- Enter the line current drawn by the balanced load.
- Enter the power factor (from the motor nameplate or a power meter) and click "Calculate".
Worked example
A balanced three-phase motor runs on VL = 400 V, draws IL = 10 A at a power factor of 0.8.
P = √3 × 400 × 10 × 0.8 = 1.732 × 3200 = 5542.56 W ≈ 5.54 kW.
Each phase supplies P/3 = 1847.52 W ≈ 1.85 kW (in star, each phase sees 400/√3 = 230.94 V at 10 A).
FAQ
Where does the √3 come from?
The three phase voltages are 120° apart, so the line-to-line voltage is √3 times the phase voltage. Combining the three phases' power, P = 3 × Vphase × Iphase × cos φ, turns into √3 × VL × IL × cos φ when written with line values.
Does the formula work for both star and delta?
Yes — as long as you use line voltage and line current, P = √3 VL IL cos φ holds for both connections in a balanced system. Only the phase values differ: in delta, Vphase = VL and Iphase = IL/√3.
Why does the power factor matter so much?
Motors and other inductive loads draw current that is partly out of step with the voltage. At cos φ = 0.8, only 80% of the apparent power (√3 VL IL) does useful work — the rest circulates as reactive power and still heats the cables.