AC Power Calculator – Real, Apparent & Reactive Power (P, S, Q)

Use this free AC Power Calculator to split an AC load into real power P, apparent power S and reactive power Q. Enter the RMS voltage, RMS current and the phase angle between them — only the part of the current in step with the voltage does useful work.

φ P (W) Q (var) S (VA) the power triangle: S² = P² + Q²

Formula

P = Vrms × Irms × cos φ  •  S = Vrms × Irms  •  Q = Vrms × Irms × sin φ  •  power factor = cos φ

How to use

Worked example

A motor runs on 230 V RMS, draws 5 A RMS, with the current lagging by φ = 30°.
S = 230 × 5 = 1150 VA.
P = 1150 × cos 30° = 1150 × 0.866 = 995.93 W — this is the power that does work and appears on the bill.
Q = 1150 × sin 30° = 575 var, and the power factor is cos 30° = 0.87.

FAQ

What is the difference between P, S and Q?
S (volt-amperes) is the total power the supply must deliver. P (watts) is the useful part converted to work, heat or light. Q (vars) is the part that sloshes back and forth into magnetic and electric fields each cycle without doing net work.

Why do electricity companies care about power factor?
A low power factor means more current for the same useful watts, which heats cables and loads transformers. Industrial users are often charged extra unless they correct the power factor, usually with capacitors.

Can reactive power be negative?
Yes. By convention Q is positive for inductive loads (motors, coils) and negative for capacitive loads. That sign is exactly why adding capacitors can cancel a motor's reactive power.