RMS Converter Calculator – Peak, RMS & Peak-to-Peak Voltage and Current
Use this free RMS Converter to change an AC voltage or current between peak, RMS and peak-to-peak values. Datasheets and oscilloscopes often quote the peak, while meters and nameplates quote RMS — this converts between them for a pure sine wave.
Formula
Vrms = Vpeak / √2 • Vpeak = √2 × Vrms • Vpp = 2 × Vpeak (for a sine wave, √2 ≈ 1.414)
How to use
- Choose whether you are converting a voltage or a current.
- Type the value you know and say whether it is the peak, the RMS or the peak-to-peak value.
- Click "Calculate" to see all three values side by side.
Worked example
A mains waveform measured on an oscilloscope peaks at 325 V.
Vrms = 325 / √2 = 229.81 V — the familiar "230 V" supply.
Vpp = 2 × 325 = 650 V from the bottom of one half-cycle to the top of the next.
FAQ
What does RMS actually mean?
Root Mean Square: the DC value that would deliver the same average power to a resistor. A 230 V RMS AC supply heats a heater exactly like 230 V DC, even though its peaks reach 325 V.
Do these factors work for square or triangle waves?
No. The √2 and 2× factors are for sine waves only. A square wave has Vrms = Vpeak, and a triangle wave has Vrms = Vpeak/√3.
Why do multimeters sometimes disagree with oscilloscopes?
Scopes show the peak directly, while most meters display RMS. Cheap meters assume a sine wave and just scale the average, so they read wrongly on distorted waveforms — a true-RMS meter measures the heating effect properly.