Wall Heat Transfer Calculator – U-Value & Heat Loss Through Layered Walls

Use this free Wall Heat Transfer Calculator to find the heat flow through a layered wall (up to 3 layers) using Q = UAΔT. Enter the area, the temperature difference and each layer's thickness and thermal conductivity — the tool adds the layer resistances, works out the total R-value and U-value, and gives the heat loss in watts.

HOT 1 2 3 COLD heat Q leaks out layers in series

Formula

Each layer has a thermal resistance R = d/(kA) (K/W). Layers in series add: Rtotal = R₁ + R₂ + R₃. The overall heat transfer coefficient (U-value) is U = 1/(Rtotal × A) in W/m²·K, and the heat flow is Q = UAΔT = ΔT/Rtotal — where d is thickness (m), k is thermal conductivity (W/m·K), A is area (m²) and ΔT is the temperature difference across the whole wall (K).

How to use

Worked example

A wall of area 10 m² with ΔT = 20 K has three layers: brick (d = 0.2 m, k = 0.8), insulation (d = 0.05 m, k = 0.04) and plaster (d = 0.02 m, k = 0.5).
R₁ = 0.2/(0.8 × 10) = 0.025 K/W · R₂ = 0.05/(0.04 × 10) = 0.125 K/W · R₃ = 0.02/(0.5 × 10) = 0.004 K/W
Rtotal = 0.025 + 0.125 + 0.004 = 0.154 K/W
U = 1/(0.154 × 10) = 0.65 W/m²·K
Q = ΔT/Rtotal = 20/0.154 = 129.87 W of heat escapes through the wall.

FAQ

Why do the resistances simply add up?
Because the same heat must pass through each layer one after another, just like electrical resistors in series. The layer with the biggest R (here the thin insulation, 0.125 K/W) does most of the insulating.

What is a U-value?
The U-value tells you how much heat passes through 1 m² of the wall for each kelvin of temperature difference. Lower is better: well-insulated modern walls have U ≈ 0.3 W/m²·K or less, while a single brick wall is around 2 W/m²·K.

Does a bigger wall change the U-value?
No — U depends only on the layers (their d and k), not on the area. A bigger area lowers the total R and so lets more total heat Q through, but the U-value stays the same.