Refrigeration COP Calculator – Refrigerator & Heat Pump COP
Use this free Refrigeration COP Calculator to find the coefficient of performance of a refrigerator or a heat pump. For a refrigerator COP = QL/W (heat removed from the cold space per unit of work); for a heat pump COP = QH/W (heat delivered to the warm space per unit of work).
Formula
Coefficient of performance: refrigerator COP = QL/W; heat pump COP = QH/W. Since QH = QL + W, the two are linked: COPheat pump = COPfridge + 1 for the same machine. COP is a ratio, so Q and W just need the same units (joules, or watts for a running machine).
How to use
- Choose refrigerator or heat pump — the heat input box changes to match (QL removed, or QH delivered).
- Enter that heat and the work input W, in the same units.
- Click "Calculate COP". The other heat (QH or QL) is shown too, from QH = QL + W.
Worked example
A refrigerator removes QL = 600 J of heat from its cold space using W = 200 J of work:
COP = QL/W = 600 / 200 = 3.0
It dumps QH = 600 + 200 = 800 J into the room, so the same machine used as a heat pump would have COP = 800/200 = 4.0.
FAQ
How can a COP be bigger than 1 — isn't that over 100% efficient?
COP is not an efficiency. The machine does not create energy; it moves heat. Moving 600 J of heat with 200 J of work breaks no law — the total energy (800 J) is exactly conserved.
What COP do real fridges and heat pumps have?
Typical home refrigerators run at COP ≈ 2–3, air conditioners ≈ 3–4, and good heat pumps ≈ 3–5 — one reason heat pumps heat a house far more cheaply than an electric bar heater (whose "COP" is only 1).
What is the maximum possible COP?
The Carnot limit: COPfridge,max = TL/(TH − TL) with temperatures in kelvin. Real machines always fall short of it because of friction and other losses.