Power Factor Correction Calculator – Capacitor kVAR to Reach Target PF
Use this free Power Factor Correction Calculator to size the capacitor bank a factory or workshop needs: enter the real load in kW and the power factor now and the power factor you want — the tool finds the reactive power (kVAR) the capacitors must supply, plus an equivalent single-phase capacitance at your voltage.
Formula
Qc = P × (tan φ1 − tan φ2), where φ = cos−1(power factor) • equivalent single-phase capacitance: C = Qc / (2πf V²)
How to use
- Enter the load's real power in kW (from the meter or nameplate).
- Enter the present power factor and the target — utilities usually want 0.95 or better.
- Optionally enter your voltage and frequency for a capacitance estimate; click "Calculate" for the capacitor kVAR rating needed.
Worked example
A plant draws P = 100 kW at power factor 0.7 and must reach 0.95.
φ1 = cos−1(0.7) = 45.57°, tan φ1 = 1.02.
φ2 = cos−1(0.95) = 18.19°, tan φ2 = 0.33.
Qc = 100 × (1.02 − 0.33) = 69.15 kVAR of capacitance.
As a single-phase equivalent at 400 V, 50 Hz: C = 69 150 / (2π × 50 × 400²) = 1375.74 µF.
FAQ
Why correct the power factor at all?
A low power factor forces the supply to carry extra current that does no work — heating cables, loading transformers and often triggering penalty charges. Capacitors supply the magnetising vars locally, so the grid current falls.
Can you over-correct past 1.0?
Yes — too much capacitance makes the power factor leading, which can raise voltages and cause its own problems. Correct to about 0.95–0.98 lagging, never beyond unity at full load.
Is the capacitance the value I buy for a three-phase bank?
The kVAR figure (69.15 kVAR here) is what you specify — it is the same for any connection. The µF figure is a single-phase equivalent; a three-phase bank splits its capacitance between delta or star arms, so buy by kVAR rating, not by µF.