Head Loss Calculator – Darcy–Weisbach Friction Loss & Pressure Drop
Use this free Head Loss Calculator to find the friction head loss in a pipe with the Darcy–Weisbach equation. Friction against the pipe wall steadily drains pressure along a pipeline — this tool gives both the head loss in metres and the equivalent pressure loss.
Formula
Darcy–Weisbach: hf = f × (L/D) × (v² / 2g) and ΔP = ρ g hf
The friction factor f depends on the Reynolds number and pipe roughness (typically 0.01–0.03 for turbulent water flow in commercial pipe). Head loss grows with the square of velocity, so doubling the flow roughly quadruples the loss.
How to use
- Enter the friction factor (0.02 is a typical default for water in smooth pipe).
- Enter pipe length, diameter and flow velocity.
- Enter the fluid density (1,000 kg/m³ for water) and click "Calculate Head Loss" for hf and ΔP.
Worked example
Water flows at 2 m/s through 100 m of pipe of diameter 0.1 m with f = 0.02. hf = 0.02 × (100 / 0.1) × (2² / (2 × 9.81)) = 0.02 × 1,000 × 0.2039 = 4.08 m of head. The pressure loss is ΔP = 1,000 × 9.81 × 4.08 = 40,000 Pa = 40 kPa — the pump must supply at least this much extra pressure just to overcome friction.
FAQ
What is "head" and why is it in metres?
Head expresses energy per unit weight of fluid as an equivalent height of that fluid. A head loss of 4.08 m means the friction consumes as much energy as lifting the water 4.08 m — or a pressure of ρgh.
How do I find the friction factor?
From the Moody chart using the Reynolds number and the pipe's relative roughness. Smooth plastic pipe in turbulent flow sits near 0.01–0.02; old, rough steel can reach 0.04 or more.
Does this include bends and valves?
No — this is straight-pipe (major) loss only. Fittings add "minor" losses, usually handled with equivalent lengths or loss coefficients added separately.